HART Procedures Procedural Considerations
Release 0 34-ST-25-20 MC Toolkit User Manual 65
7/03
Table 20 HART Calibration - Zero Trim (non-Honeywell Transmitter)
HART Calibration - Zero Trim (non-Honeywell Transmitter)
Overview of
Objective
Requirements:
· Precision input source
· (See Note at right.)
Overview:
The Zero-Trim procedure
establishes zero reference
point of the input-response
profile.
Note:
This procedure outlines the steps for using the MC Toolkit
with various non-Honeywell HART transmitters.
For specific requirements, refer to the user manual for the
transmitter being calibrated.
Zero Trim
Select Zero Trim. The first
of a series of pop-up message
appears.
Apply the zero-reference
input source to the sensor.
Wait for the message at right
to appear.
Then, select the OK button.