HART Procedures Procedural Considerations
Release 0 34-ST-25-20 MC Toolkit User Manual 57
7/03
Table 17 Honeywell HART Calibration - Apply Values
Honeywell HART Calibration - Apply Values
Overview
of
Objectives
· Manually set Process Variable input to 0%, and apply this value to Set LRV (output) at
4 MA.
· Manually set Process Variable input to 100%, and apply this value to set URV (output)
at 20 mA.
(Adjust
and View
Process
Variable
input value
at LRV.)
This function uses actual
process values to calibrate
input of LRV and URV.
Physically observe the value
of the Process Variable, and
adjust it manually to the
desired LRV value.
Select the Apply Values
button on the Calibration
menu; the display at right
appears.
Select the Send button.
This popup message
appears.