QuickSpecs
hp StorageWorks NAS 8000
DA-11511 World Wide — Version 1 — October 16, 2002 9
POWER SPECIFICATIONS
Power Supply Part Number 192147-001
Power Supply Spare Kit 278535-B21
Operational Input Voltage Range (V rms)
90 to 264
Frequency Range (Nominal) (Hz)
47 to 63 (50/60)
Nominal Input Voltage (Vrms)
100 115 208 220 230 240
Max Rated Output Wattage Rating
800 800 800 800 800 800
Nominal Input Current (A rms)
12.0 10.2 5.2 4.9 4.7 4.5
Max Rated Input Wattage Rating (Watts)
1143 1111 1067 1067 1067 1053
Max. Rated VA (Volt-Amp)
1203 1170 1088 1088 1088 1074
Efficiency (%)
70 72 75 75 75 76
Power Factor
0.95 0.95 0.98 0.98 0.98 0.98
Leakage Current (mA)
0.43 0.50 .90 .96 1.00 1.04
Maximum Inrush Current (A peak)
25 25 25 25 25 25
Maximum Inrush Current duration (mS)
20 20 20 20 20 20
SYSTEM SPECIFICATIONS
NAS Server Fully Configured
Up to 4 Processors, 16 Memory Slots, 4 Hard Drives, 6 PCI Slots, and 2 Hot Plug Power Supplies
Nominal Input Voltage (Vrms)
100 115 208 220 230 240
Fully Loaded System Input Wattage (W)
1068 1068 1025 1025 1025 1012
Fully Loaded System Input AMPs (A rms)
11.6 9.8 5.0 4.8 4.5 4.3
Fully Loaded System Thermal (BTU-Hr)
3746 3642 3496 3496 3496 3450
Fully Loaded System VA (Volt-Amp)
1156 1124 1046 1046 1046 1032
System Leakage with all power supplies loaded
(mA)
.87 1.00 1.81 1.91 2.00 2.09
System Inrush Current with all power supplies
loaded (A)
50 50 50 50 50 50
Nema 5-15P to IEC320-C19 Option no./Spare no: 235603-001/237457-001
Power cord requirements
PDU Jumper Cord IEC320-C19 to
IEC320-C20
Option no./Spare no: 295633-B21/295508-001
NOTES:
ActiveAnswers Power Calculation.
Power calculator is LIVE on ActiveAnswers website:
http://activeanswers.compaq.com/aaconfiguratorcode/configurationUi.asp?HTMLFilename=Mainselections&UiLocalization=
UnitedStates&DisplayCountry=United%20States
To drill down to calculators:
- Click on: “ProLiant Servers”
- Click on the Server of interest. Example: DL580 G2
- Click on: “Power Calculator” link (You may need to scroll down to see it.)
Seitenansicht 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 17 18

Kommentare zu diesen Handbüchern

Keine Kommentare